Symptom Troubleshooting Solutions
When using multiple MPR-50s, network
topology errors occur.
Ensure that the internal channel of each
of the MPR-50s in the network is defined
within the network tool as a separate
channel.
The MPR-50 does not pass messages larger
than 114 bytes.
The MPR-50 can support messages up to
256 bytes. Configure the router buffers
using the application described in
Appendix A, Buffer Configuration
Utility.
MPR-50 Multi-Port Router User's Guide 33