SmartServer 2.2 User’s Guide 119
15. At the end of the upgrade process, the i.LON AdminServer will display the following error
message: “Failed I/O error: Connection refused: connect; nested exception is
java.net.ConnectException”. As a result, you cannot open the SmartServer 2.2 Web pages until
you reboot the SmartServer with the console application.
16. Reboot your SmartServer by entering the reboot command in the console application. For more
information on the SmartServer console application, see Appendix B, Using the SmartServer
Console Application..
17. When the reboot has been completed, you can open the SmartServer 2.2 Web pages.
Restoring a SmartServer to Factory Default Settings
You can restore your SmartServer to its factory default settings with the SmartServer Web pages or the
console application. To perform a factory default reset, secure access mode must be enabled on your
SmartServer (see Enabling and Disabling Secure Access Mode in this chapter for more information on
enabling secure access on your SmartServer).
To restore your SmartServer to its factory default settings with the SmartServer Web pages, follow
these steps:
1. Right-click the SmartServer icon, point to Setup, and then click Cleanup on the shortcut menu.
2. The Setup Cleanup dialog opens.