SmartServer 2.2 User’s Guide 333
6. A functional block representing the Alarm Generator application and all of its static data points are
added to the bottom of the i.LON App (Internal) device tree, and the Alarm Generator:
Configure Web opens in the application frame to the right. The construction symbol overlaid
onto the Alarm Generator application icon in the upper-left hand corner of the Web page indicates
that the application has not been configured yet.
7. Click Submit.